Technical Data Sheet

CAT6 UTP 23AWG COPPER

Construction

Conductor Solid Bare Copper & Conductor Dia.: 0.57 ± 0.003mm
Insulation Raw material of the insulation: PE 4 Twisted Pairs :          Blue/white-blue;             Green / white-green; Orange/white-orange;  Brown / white-brown;                                                 Insulation Dia. : 1.02 ± 0.005mm Average thickness: 0.2125mm Minimum point thickness: 0.21mm
Separator Center cross
Rip Cord Nylon thread
Jacket Jacket Material                       :           PVC Color                                       :           Sky Blue Nominal Dia.                           :           6.3 ± 0.2mm Average thickness                   :           0.60mm Minimum point thickness       :           0.50mm

Application

Primary(Campus), Secondary(Riser), Tertiary(Horizontal)

IEEE802.3: 10 Base-T ; 100 Base-T ; 1000 Base-t ;

IEEE802.5 16MB ; RDSI/ISDN; 100 Mbps TPDDI; 155 Mbps ATM

Standard

TIA/EIA 568.BEN50173-1
IEC/ISO11801EN50288-6-1

Packing

305 Meter Pull Box

Mechanical Properties

Minimum Bending Radius

Installation:              8×O.D.

Installed:                  4×O.D.

Temperature Range

During operation:    -55 °C — +60 °C

During installation:  -15 °C — +50 °C

Max Tensile Load

During operation:    —

During installation:  110N

Electrical Properties

Resistance unbalance ≤ 2%
Loop impedance ≥110 MΩ/km
Capacitance 230pF/m
Capacitance unbalance ≤330 pF/100m
Characteristic impedance 1-100Mhz: (100±15) Ω
Nominal velocity of propagation ≥Approximate 62%
Propagation delay ≤537 ns/100m @ 100mhz
Delay skew Nominal 45 ns/100m, 1-250 Mhz
Test voltage (DC, 1 min) 1000v

Nominal Transmission Characteristics